• Title of article

    Numerical study of the thermal–hydraulic performance of evaporative natural draft cooling towers

  • Author/Authors

    M.N.A Hawlader، نويسنده , , B.M. Liu، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    19
  • From page
    41
  • To page
    59
  • Abstract
    In this paper, the mathematical and physical models governing the flow, mass and heat energy of moist have been set up for an evaporative natural draft cooling tower. The models consider the effect of non-spherical shape of water drops on the flow, heat and mass transfer. Experimental data has been adopted to validate the numerical scheme. Average difference between the measured and the predicted outlet water temperature is 0.26°C. Distributions of the velocity components of the moist air, density, pressure, enthalpy and moisture content, the water temperature and its mass flux have been predicted. The simulation shows that some recirculation exits under the lower edge of the shell, where the air enthalpy, temperature, humidity and moisture content are higher, but the density is lower. The simulation also proves that the main transfer processes take place in the fill region where the percentage of latent heat transfer is predicted as 83%. However, about 90% of the heat energy is transferred via evaporation in the rain region although the total heat transfer rate there is very small compared to the fill region. Hourly performance of a natural draft cooling tower under the meteorological condition of Singapore has also been predicted.
  • Keywords
    Distributions of flow , Heat and mass transfer , Hourly performance , Cooling tower , Numerical study , Mathematical and physical models , Non-spherical effects , validation
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2002
  • Journal title
    Applied Thermal Engineering
  • Record number

    1023413