• Title of article

    Experimental study of a low temperature heat driven re-heat two-stage adsorption chiller

  • Author/Authors

    K.C.A. Alam، نويسنده , , M.Z.I. Khan، نويسنده , , A.S. Uyun، نويسنده , , Y. Hamamoto، نويسنده , , A. Akisawa، نويسنده , , T. Kashiwagi، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    7
  • From page
    1686
  • To page
    1692
  • Abstract
    The performance of an advanced adsorption chiller, namely, ‘reheat two-stage’ has been investigated experimentally in the present study. The performances in terms of specific cooling power (SCP) and COP are compared with those of conventional single and two-stage chiller. Results show that the reheat two-stage chiller provides more SCP values than those provided by conventional single-stage chiller while it provides better COP values for relatively low heat source temperature. The reheat two-stage chiller also provides almost same cooling capacity comparing with two-stage chiller for the low temperature heat source, while it provides higher COP value than that provided by two-stage chiller. Experimental results also show that the overall performance of the reheat two-stage chiller is always higher than that of conventional single and two-stage adsorption cycle even the temperature of the heat source is fluctuated between 55 and 80 °C.
  • Keywords
    COP , Adsorption , Reheat two-stage , Low temperature heat source , Specific cooling power
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2007
  • Journal title
    Applied Thermal Engineering
  • Record number