Title of article
Experimental study of a solid adsorption cooling system using flat-tube heat exchangers as adsorption bed
Author/Authors
W.-S. Chang، نويسنده , , C.-C. Wang، نويسنده , , C.-C. Shieh، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
5
From page
2195
To page
2199
Abstract
In this paper, a solid adsorption cooling system with silica gel as the adsorbent and water as the adsorbate was experimentally studied. To reduce the manufacturing costs and simplify the construction of the adsorption chiller, a vacuum tank was designed to contain the adsorption bed and evaporator/condenser. Flat-tube type heat exchangers were used for adsorption beds in order to increase the heat transfer area and improve the heat transfer ability between the adsorbent and heat exchanger fins. Under the standard test conditions of 80 °C hot water, 30 °C cooling water, and 14 °C chilled water inlet temperatures, a cooling power of 4.3 kW and a coefficient of performance (COP) for cooling of 0.45 can be achieved. It has provided a specific cooling power (SCP) of about 176 W/(kg adsorbent). With lower hot water flow rates, a higher COP of 0.53 can be achieved.
Keywords
Flat-tube type heat exchanger , Adsorption cooling
Journal title
Applied Thermal Engineering
Serial Year
2007