Title of article
An experimental study on variable air volume operation of ducted air-conditioning with digital scroll compressor and conventional scroll compressor
Author/Authors
Hu Huang، نويسنده , , Qihe Li، نويسنده , , Dongxue Yuan، نويسنده , , Zhenchun Qin، نويسنده , , Zhongbin Zhang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
6
From page
761
To page
766
Abstract
An experimental study on operation characteristics with variable air volume under refrigerating and heating condition of ducted air-conditioning (AC) unit with digital scroll compressor and conventional scroll compressor is conducted in this paper. The effects of air volume on the refrigerating (heating) capacity, input power, EER (COP), outlet temperature, discharge pressure, discharge temperature and suction pressure are studied. Compared with the ducted air-conditioning unit with conventional scroll compressor, the experimental results are the outlet temperature of ducted AC unit with digital scroll compressor is stable; the suction pressure and discharge pressure are normal; the discharge temperature drops a bit; the input power is lower. This shows that the unit with digital scroll compressor is well adapted to the variable air volume running and good for the economical and reliable operation of the ducted AC unit.
Keywords
Refrigerating , Heating , Variable air volume , Ducted unit , Digital scroll compressor
Journal title
Applied Thermal Engineering
Serial Year
2008
Journal title
Applied Thermal Engineering
Record number
1041571
Link To Document