Title of article
Performance characterisation of liquid desiccant columns for a hybrid air-conditioner
Author/Authors
B. Shaji Mohan، نويسنده , , M. Prakash Maiya، نويسنده , , Shaligram Tiwari، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
14
From page
1342
To page
1355
Abstract
Use of liquid desiccant-vapor compression hybrid system is encouraged for low humidity applications. The liquid desiccant is primarily used to further dehumidify the supply air. In the present study, by using psychrometric equations and liquid desiccant property data, heat and mass transfer analysis for the dehumidifier and regenerator columns in counter flow configuration has been carried out. The simulation of the columns corresponds to low solution to air (S/A) flow ratio where precooled air gets dehumidified in the absorber while preheated air is used for regeneration of the solution. A detailed study of the performance characteristics for the absorber and regenerator columns confirms the requirement of the desiccant loop for additional dehumidification of the conditioned air. This need develops the main motive towards the concept of hybrid air conditioning.
Keywords
Liquid desiccant , Dehumidification , Vapor compression , Regeneration , Hybrid System
Journal title
Applied Thermal Engineering
Serial Year
2008
Journal title
Applied Thermal Engineering
Record number
1041635
Link To Document