• Title of article

    CFD analysis of a supersonic air ejector. Part I: Experimental validation of single-phase and two-phase operation

  • Author/Authors

    Amel Hemidi، نويسنده , , Jean François Henry، نويسنده , , Sébastien Leclaire، نويسنده , , Jean-Marie Seynhaeve، نويسنده , , Yann Bartosiewicz، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    9
  • From page
    1523
  • To page
    1531
  • Abstract
    This paper deals with comparisons between CFD and experiments for a supersonic ejector. Good results are presented in terms of entrainment rate compared to home-made experimental data for an air ejector. Over the whole range of operating conditions, the overall deviation is below 10% for the image model, while the results for the image model are in a less agreement. Furthermore, it is demonstrated that the validation of a global performance parameter, such as the entrainment rate, is not sufficient for a correct assessment even though a wide range of operation is tried out. Indeed, for exactly the same prediction both models may give very different local flow features. Finally, a first attempt to tackle two-phase aspects was also performed experimentally and by simulations.
  • Keywords
    Air-conditioning , Turbulence models , Supersonic ejector , CFD-experiment integration , Two-phase compressible flows
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2009
  • Journal title
    Applied Thermal Engineering
  • Record number