    Experimental study of impingement spray cooling for high power devices

  • Author/Authors

    Z.B. Yan، نويسنده , , K.C. Toh، نويسنده , , F. Duan، نويسنده , , T.N. Wong، نويسنده , , K.F. Choo، نويسنده , , P.K. Chan، نويسنده , , Y.S. Chua، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2010
  • Pages
    6
  • From page
    1225
  • To page
    1230
  • Abstract
    An experimental study of a closed-loop impingement spray cooling system to cool a 1 kW 6U electronic test card has been conducted. The system uses R134a as working fluid in a modified refrigeration cycle. The spray from four vapor assisted nozzles is arranged to cover a large ratio of the heated area of the card. Investigations are currently focused on effects of mass flow rate, nozzle inlet pressure and spray chamber pressure. Experimental results are promising with a stable average temperature of around 23 °C being maintained at the heated surface, and maximum temperature variation of about 2 °C under suitable operating conditions. Heat transfer coefficients up to 5596 W/m2 K can be achieved with heat flux input around 50,000 W/m2 in this study. It is found that cooling performance improved with increasing mass flow rate, nozzle inlet pressure and spray chamber pressure, whereas uniformity of the heated surface temperature can only be improved with higher mass flow rate and nozzle inlet pressure. The mechanisms for the enhanced performance are also presented.
  • Keywords
    Large area , High power electronic card , Closed loop , Impingement spray cooling