Title of article
Heat and momentum transfer for compact louvered fin-and-tube heat exchangers in wet conditions
Author/Authors
Chi-Chuan Wang، نويسنده , , Yur-Tsai Lin، نويسنده , , Chi-Juan Lee، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2000
Pages
10
From page
3443
To page
3452
Abstract
The air side performances of two louvered fin surfaces under dehumidifying conditions were examined in this study. The test results indicated that the effect of fin pitch on the heat transfer performance is comparatively small, and the friction factors increase significantly with fin pitch for fully wet conditions. The effect of inlet relative humidity on the sensible heat transfer performance is negligible. However, there is a detectable effect of inlet condition on the friction factors for type (I) louver due to condensate retention. A correlation of heat, momentum, and mass transfer was proposed to correlate the present database with a mean deviation of 5.94%, 6.1%, and 7.89%, respectively.
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2000
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1070186
Link To Document