• Title of article

    Fouling characteristics of internal helical-rib roughness tubes using low-velocity cooling tower water

  • Author/Authors

    Wei Li، نويسنده , , Ralph L. Webb، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    7
  • From page
    1685
  • To page
    1691
  • Abstract
    This paper provides long-term cooling tower water fouling data in seven 15.54 mm I.D. copper, helically ribbed tubes taken at low water velocity (1.07 m/s). The ranges of geometric parameters were number of rib starts (18–45), helix angle (25–45°), and height (0.33–0.55 mm). These geometries provide a new class of internal enhancement that is typical of commercially enhanced tubes presently used in water chillers. There are two ranges of fouling characteristics based on internal dimensions: linear range and non-linear range. The ratio of the enhanced-to-plain tube fouling resistance linearly increases with increasing the product of area indexes and efficiency indexes in linear range and the linear relationship fails in non-linear range. A series of semi-theoretical fouling correlations as a function of the product of area indexes and efficiency indexes were developed. They were applicable to different internally ribbed geometries within the above dimensional range. A series of linear multiple regression correlations as a function of geometric variables and Reynold numbers were also developed. The average deviation of the two series of correlations was 4.4% and 4.8%, respectively. The correlations can be directly used to assess the fouling potential of enhanced tubes in actual cooling water situations.
  • Keywords
    Fouling , Cooling tower , Enhanced tube , Turbulent flow
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Serial Year
    2002
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Record number

    1070819