Title of article
Effects of high subcooling on two-phase spray cooling and critical heat flux
Author/Authors
Milan Visaria، نويسنده , , Issam Mudawar، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
10
From page
5269
To page
5278
Abstract
Experiments were performed with FC-77 using three full-cone spray nozzles to assess the influence of subcooling on spray performance and critical heat flux (CHF) from a 1.0 × 1.0 cm2 test surface. The relatively high boiling point of FC-77 (97 °C at one atmosphere) enabled testing at relatively high levels of subcooling. Increasing the subcooling delayed the onset of boiling but decreased the slope of the nucleate boiling region of the spray boiling curve. The enhancement in CHF was relatively mild at low subcooling and more appreciable at high subcooling. CHF was enhanced by about a 100% when subcooling was increased from 22 to 70 °C, reaching values as high as 349 W/cm2. The FC-77 data were combined with prior spray CHF data from several studies into a broad CHF database encompassing different nozzles, fluids, flow rates, spray orientations, and subcoolings. The entire CHF database was used to modify the effect of subcooling in a previous CHF correlation that was developed for relatively low subcoolings. The modified correlation shows excellent predictive capability.
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2008
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1075640
Link To Document