Title of article
Physical water treatment using RF electric fields for the mitigation of CaCO3 fouling in cooling water
Author/Authors
Leonard D. Tijing، نويسنده , , Hang Young Kim، نويسنده , , Dong Hwan Lee، نويسنده , , Cheol Sang Kim، نويسنده , , Young I. Cho، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2010
Pages
12
From page
1426
To page
1437
Abstract
The present study investigated the feasibility of RF electrical fields in mitigating CaCO3 fouling in cooling water. Three different voltages and two frequencies were used for the RF electric fields produced directly in water with varying cold-side velocity. Artificial hard water was used. Fouling resistances for the PWT-treated cases decreased by 34–88% from the values for no-treatment cases, depending on the cold-side flow velocity. The results showed blunt crystal structures for the PWT-treated cases, while no-treatment cases had sharp and pointed crystal structures. The new PWT method using RF electric fields presents a valid tool to mitigate CaCO3 fouling in cooling water.
Keywords
Physical water treatment , RF electric field , CaCO3 fouling , Fouling resistance
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2010
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1076546