• Title of article

    Air-side heat transfer characteristics of flat plate finned-tube heat exchangers with large fin pitches under frosting conditions

  • Author/Authors

    Mooyeon Lee، نويسنده , , Yonghan Kim، نويسنده , , Hosung Lee، نويسنده , , Yongchan Kim، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2010
  • Pages
    7
  • From page
    2655
  • To page
    2661
  • Abstract
    The air-side heat transfer characteristics of flat plate finned-tube heat exchangers were measured and analyzed by varying the fin pitch, number of tube rows, and tube alignment under frosting conditions. Two empirical correlations for predicting the j-factor were developed separately for the inline and the staggered tube alignment, respectively, as a function of the Reynolds number, Fourier number, number of tube rows, and dimensionless hydraulic diameter normalized by fin pitch. The average deviation of the predictions of the present correlations from the measured data was 1.31% for the inline tube alignment and 0.65% for the staggered tube alignment.
  • Keywords
    Finned-tube heat exchanger , Frost , j-factor , Pressure drop , correlation
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Serial Year
    2010
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Record number