• Title of article

    Conflation of ε-Ntu and EGM design methods for heat exchangers with uniform wall temperature

  • Author/Authors

    Christian J.L. Hermes، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    6
  • From page
    3812
  • To page
    3817
  • Abstract
    This paper conflates two heat exchanger design approaches – the ε-Ntu (effectiveness–number of transfer units) and the EGM (entropy generation minimization) – focusing on heat exchangers with uniform wall temperature, i.e. condensers and evaporators. An algebraic formulation which expresses the dimensionless rate of entropy generation as a function of the heat exchanger geometry (number of transfer units), the thermal-hydraulic characteristics (friction factor and Colburn j-factor), and the operating conditions (heat transfer duty, core velocity, surface temperature, and fluid properties) is derived. It is shown that there does exist a particular number of transfer units which minimizes the dimensionless rate of entropy generation. An algebraic expression for the optimum heat exchanger effectiveness, based on the working conditions, heat exchanger geometry and fluid properties, is also presented. The theoretical analysis led to the conclusion that a high effectiveness heat exchanger design does not necessarily provide the best thermal-hydraulic performance.
  • Keywords
    design , condenser , Evaporator , Number of transfer units , Optimization , Minimum entropy generation
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Serial Year
    2012
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Record number