Title of article
Windbreak walls reverse the negative effect of crosswind in short natural draft dry cooling towers into a performance enhancement
Author/Authors
Y. Lu، نويسنده , , Z. Guan، نويسنده , , and H. Gurgenci، نويسنده , , Z. Zou، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
9
From page
162
To page
170
Abstract
Crosswind effect on the cooling performance of large natural draft dry cooling towers (NDDCT) has been verified to be unfavourable by many researchers. Small size natural draft cooling towers (height <30 m) proposed for geothermal and other renewable power plants are expected to be more negatively affected. CFD modelling has been carried out to numerically analyse the heat transfer performance of a 15 m-high small NDDCT under different crosswind speeds. Simulations show that, at certain crosswind speeds, the crosswind significantly degrades the cooling performance. However, the negative effect of the crosswind can be turned into positive in small natural draft cooling towers by introducing windbreak walls that guide the air mobilised by crosswind through the heat exchangers. When windbreak walls are used, the results show that the tower performance improves with increased crosswind velocity.
Keywords
Numerical simulation , Crosswind , Windbreak wall , Natural draft cooling tower , CFD modelling
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2013
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1078944
Link To Document