Title of article
An experimental study on ventilation efficiency of isolation room
Author/Authors
Yun-Chun Tung، نويسنده , , Shih-Cheng Hu، نويسنده , , Tung-I Tsai، نويسنده , , I-Lang Chang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2009
Pages
9
From page
271
To page
279
Abstract
This paper presents an experimental modeling of contaminant dispersion in a mock-up isolation room with different negative pressure differentials and ventilation rates. A hypothetical contaminant (sulfur hexafluoride, SF6) is emitted from a patient lying on a bed in the mock-up isolation room. The impacts of ventilation rates 12 and 24 h−1 and pressure differentials −2.5, −5.0, −8.0, and −15.0 Pa on the ventilation effectiveness in the room are evaluated quantitatively. A local air quality index and an exposure index for healthcare workers are introduced in the research to evaluate the ventilation efficiency of the isolation room. Based on the results of our experiment, the ventilation efficiency of the isolation room ranks the highest at −15.0 Pa/24 h−1, followed, respectively, by −15.0 Pa/12 h−1, −8.0 Pa/24 h−1, −5.0 Pa/24 h−1, −2.5 Pa/24 h−1, −8.0 Pa/12 h−1, −5.0 Pa/12 h−1, and −2.5 Pa/12 h−1.
Keywords
Isolation room , pressure differential , Airborne contaminant , ventilation
Journal title