• Title of article

    An experimental study on ventilation efficiency of isolation room

  • Author/Authors

    Yun-Chun Tung، نويسنده , , Shih-Cheng Hu، نويسنده , , Tung-I Tsai، نويسنده , , I-Lang Chang، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    9
  • From page
    271
  • To page
    279
  • Abstract
    This paper presents an experimental modeling of contaminant dispersion in a mock-up isolation room with different negative pressure differentials and ventilation rates. A hypothetical contaminant (sulfur hexafluoride, SF6) is emitted from a patient lying on a bed in the mock-up isolation room. The impacts of ventilation rates 12 and 24 h−1 and pressure differentials −2.5, −5.0, −8.0, and −15.0 Pa on the ventilation effectiveness in the room are evaluated quantitatively. A local air quality index and an exposure index for healthcare workers are introduced in the research to evaluate the ventilation efficiency of the isolation room. Based on the results of our experiment, the ventilation efficiency of the isolation room ranks the highest at −15.0 Pa/24 h−1, followed, respectively, by −15.0 Pa/12 h−1, −8.0 Pa/24 h−1, −5.0 Pa/24 h−1, −2.5 Pa/24 h−1, −8.0 Pa/12 h−1, −5.0 Pa/12 h−1, and −2.5 Pa/12 h−1.
  • Keywords
    Isolation room , pressure differential , Airborne contaminant , ventilation
  • Journal title
    Building and Environment
  • Serial Year
    2009
  • Journal title
    Building and Environment
  • Record number

    1217524