• Title of article

    Influence of oil on R-410A two-phase frictional pressure drop in a small U-type wavy tube

  • Author/Authors

    I.Y Chen، نويسنده , , C.L. Won، نويسنده , , C.C. Wang، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    12
  • From page
    797
  • To page
    808
  • Abstract
    This study presents single-phase and two-phase pressure drop data with oil concentration C = 0, 1, 3 and 5% in a copper wavy tube having an inner diameter of 3.25 mm and a curvature radius of 6.35 mm. The ratio of frictional factor between U-bend in wavy tube and straight tube (fC/fS) is about 1.5 to 2.5 for Re = 2500 ∼ 25000. The effect of secondary flow is very crucial in the U-bend that it increases the pressure drop considerably. However, the effect of oil concentration on friction factor is negligible provided the properties are based on mixture. The ratio between two-phase pressure gradients of U-bend and straight tube is about 3. This ratio is increased with oil concentration and vapor quality. The oil effect on two-phase pressure drop is especially pronounced at high vapor quality because the effective oil concentration in liquid mixture is increased with vapor quality. The frictional two-phase multiplier for straight tube can be fairly correlated by using the Chisholm correlation. A modified two-phase friction factor based on the Geary correlation is also utilized to predict the frictional two-phase pressure gradient in U-bend. The predictions give a good agreement to the present oil–refrigerant data with a mean deviation of 12.92%.
  • Keywords
    Two-phase flow , U-type wavy tube , Oil and refrigerant , Frictional pressure drop
  • Journal title
    International Communications in Heat and Mass Transfer
  • Serial Year
    2005
  • Journal title
    International Communications in Heat and Mass Transfer
  • Record number

    1219924