• Title of article

    Laboratory simulation of direct lightning strokes to a modeled building: measurement of magnetic fields and induced voltages

  • Author/Authors

    W Zischanka، نويسنده , , F Heidlera، نويسنده , , J Wiesingera، نويسنده , , I Metwallya، نويسنده , , A Kernb، نويسنده , , M Seeversc، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    10
  • From page
    223
  • To page
    232
  • Abstract
    In IEC 61312-2 equations for the assessment of the magnetic fields inside structures due to a direct lightning strike are given. These equations are based on computer simulations for shields consisting of a single-layer steel grid of a given mesh width. Real constructions, however, contain at least two layers of reinforcement steel grids. The objective of this study was to experimentally determine the additional shielding effectiveness of a second reinforcement layer compared to a single-layer grid. To this end, simulated structures were set up in the high current laboratory. The structures consisted of cubic cages of 2 m side length with one or with two reinforcement grids, respectively. The structures were exposed to direct lightning currents representing the variety of anticipated lightning current waveforms. The magnetic fields and their derivatives at several positions inside the structure as well as the voltage between “floor” and “roof” in the center were determined for different current injection points. From these data the improvement of the shielding caused by a second reinforcement layer is derived.
  • Keywords
    Magneticfield , Inducedvoltage , lightning , Electromagneticshielding , Reinforcedconcrete
  • Journal title
    JOURNAL OF ELECTROSTATICS
  • Serial Year
    2004
  • Journal title
    JOURNAL OF ELECTROSTATICS
  • Record number

    1264563