• Title of article

    Evaluation of heat and mass transfer coefficients in a gauze-type structured packing air dehumidifier operating with liquid desiccant

  • Author/Authors

    Al-Farayedhi، نويسنده , , Abdulghani A. and Gandhidasan، نويسنده , , P. and Al-Mutairi، نويسنده , , M.A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    10
  • From page
    330
  • To page
    339
  • Abstract
    In this paper, high performance packing, namely, structured packing that has good heat and mass transfer characteristics, is proposed for dehumidification of air using liquid desiccants and for regeneration of liquid desiccants. In order to design a structured packing tower for liquid desiccant — air contacting operations, heat and mass transfer coefficients for each phase are required. This paper is concerned with the interface transfer of heat and mass when air is brought into contact with the liquid desiccant solution. A theoretical study of evaluating heat and mass coefficients in an air-desiccant contact system employing three liquid desiccants, namely calcium chloride, lithium chloride, and a mixture of 50% calcium chloride and 50% lithium chloride (called cost effective liquid desiccant, CELD) is investigated. Moreover, air phase transfer coefficients are correlated with flow rates of air and liquid and the temperature of air, whereas liquid phase coefficients are correlated with rates of air and liquid flow, and the temperature and concentration of the liquid. The findings for the three liquid desiccants are compared and discussed.
  • Keywords
    Conception , Performance , Air , Drying , desiccant , Calcium chloride , lithium chloride , Heat Exchanger , Performance , Air , Séchage , Design , Chlorure de calcium , Chlorure de lithium échangeur de chaleur , Déshydratant
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2002
  • Journal title
    International Journal of Refrigeration
  • Record number