• Title of article

    A generalized correlation for refrigerant mass flow rate through adiabatic capillary tubes

  • Author/Authors

    Choi، نويسنده , , Jongmin and Kim، نويسنده , , Yongchan and Kim، نويسنده , , Ho Young، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2003
  • Pages
    8
  • From page
    881
  • To page
    888
  • Abstract
    A capillary tube is a common expansion device used in small sized refrigeration and air-conditioning systems. A generalized correlation for refrigerant flow rate in adiabatic capillary tubes is developed by implementing dimensionless parameters based on extensive experimental data for R-22, R-290, and R-407C measured in this study. Dimensionless parameters are derived from the Buckingham Pi theorem, considering the effects of tube inlet conditions, capillary tube geometry, and refrigerant properties on mass flow rate. The generalized correlation yields good agreement with the present data for R-22, R-290, and R-407C with average and standard deviations of 0.9 and 5.0%, respectively. Approximately 97% of the present data are correlated within a relative deviation of ±10%. Further assessments of the correlation are made by comparing the predictions with measured data for R-12, R-134a, R-152a, R-410A, and R-600a in the open literature. The correlation predicts the data for those five refrigerants with average and standard deviations of −0.73 and 6.16%, respectively.
  • Keywords
    Frigorigène , débit , Capillaire , domestic refrigerator , R-22 , Refrigerant , R-407C , Flow , R-290 , Capillary tube , Air conditioner , SIMULATION , Expansion device , Simulation , R-407C , R-22 , R-290 , Conditionneur dיair , Réfrigérateur domestique , Détente
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2003
  • Journal title
    International Journal of Refrigeration
  • Record number

    1339630