    Reasons for drop in shell-and-tube condenser performance when replacing R22 with zeotropic mixtures. Part 1. Analysis of experimental findings

  • Author/Authors

    Sajjan، نويسنده , , Dave and Karlsson، نويسنده , , Tord and Vamling، نويسنده , , Lennart، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    9
  • From page
    552
  • To page
    560
  • Abstract
    An experimental and theoretical investigation was made to find out the reasons for the drop in shell-and-tube condenser performance when replacing R22 with a zeotropic mixture R407C. Measurements show that at lower condenser loads the reduction in performance can be as large as 70% compared to the full condenser load. Calculation results are compared with experimental results for two different condensers, one with micro-finned tubes and one with 3-D finned tubes. Calculations show that the degree of mixing of the newly formed condensate on a tube and the drained condensate is a factor influential enough to explain the performance drop. 3-D finned tubes seem to have better mixing in the condensate than integral finned tubes.