Title of article
Two-fluid model of refrigerant two-phase flow through short tube orifice
Author/Authors
Yang، نويسنده , , Liang and Zhang، نويسنده , , Chun-Lu، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
9
From page
419
To page
427
Abstract
Pronounced hydrodynamic and thermodynamic non-equilibrium exist in the flow of refrigerant through a short tube orifice under typical operating conditions. A non-equilibrium two-fluid model (TFM) for refrigerant two-phase critical flow inside the short tube orifice is developed. Both inter-phase velocity slip and inter-phase temperature difference are taken into account in the model. The mass flow rate, the two-phase velocity and temperature distributions in a short tube orifice are simulated. Comparisons among the experimental data of refrigerants R134a, R12, R22, R410A and R407C flowing through short tubes, the predictions by the TFM and by the homogeneous equilibrium model (HEM) show that the TFM gives acceptable predictions with the deviations of ±20%, while the HEM underestimates the flow rate by 20% or so.
Keywords
Temperature , R-407C , R-407C , R-134a , R-12 , ةcoulement diphasique , Frigorigène , Two-phase flow , Capillaire , Modelling , Tube , Refrigerant , débit , capillary , Temperature , Distribution , R-410A , Tube , Distribution , Modélisation , R-410A , R-22 , Flow , R-134a , R-12 , R-22
Journal title
International Journal of Refrigeration
Serial Year
2005
Journal title
International Journal of Refrigeration
Record number
1339836