Title of article
Heat transfer characteristics of flat plate finned-tube heat exchangers with large fin pitch
Author/Authors
Kim، نويسنده , , Yonghan and Kim، نويسنده , , Yongchan، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2005
Pages
8
From page
851
To page
858
Abstract
The objective of this study is to provide experimental data that can be used in the optimal design of flat plate finned-tube heat exchangers with large fin pitch. In this study, 22 heat exchangers were tested with a variation of fin pitch, number of tube row, and tube alignment. The air-side heat transfer coefficient decreased with a reduction of the fin pitch and an increase of the number of tube row. The reduction in the heat transfer coefficient of the four-row heat exchanger coil was approximately 10% as the fin pitch decreased from 15.0 to 7.5 mm over the Reynolds number range of 500–900 that was calculated based on the tube diameter. For all fin pitches, the heat transfer coefficient decreased as the number of tube row increased from 1 to 4. The staggered tube alignment improved heat transfer performance more than 10% compared to the inline tube alignment. A heat transfer correlation was developed from the measured data for flat plate finned-tubes with large fin pitch. The correlation yielded good predictions of the measured data with mean deviations of 3.8 and 6.2% for the inline and staggered tube alignment, respectively.
Keywords
ةchangeur de chaleur , tube aileté , Géométrie , Coefficient de transfert de chaleur , Experiment , Heat Exchanger , Geometry , Heat transfer coefficient , Expérimentation , finned tube
Journal title
International Journal of Refrigeration
Serial Year
2005
Journal title
International Journal of Refrigeration
Record number
1339975
Link To Document