    Two bed silica gel–water adsorption chillers: An effectual lumped parameter model

  • Author/Authors

    Wang، نويسنده , , Xiaolin and Chua، نويسنده , , H.T.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2007
  • Pages
    10
  • From page
    1417
  • To page
    1426
  • Abstract
    This article develops an improved lump-parameter design model to investigate the water-circulation heat recovery scheme as applied to the two-bed silica gel–water adsorption chillers. We demonstrate that performance predictions stemming from this improved lump-parameter formalism compare favorably with experimental results at various conditions, particularly at the industrial rated conditions. We find that the present lump-parameter formalism adequately elucidates the water-circulation heat recovery scheme as does the distributed-parameter formalism. In the studied working condition of a two-bed silica gel–water adsorption chiller, the differences in cooling capacities and coefficients of performance (or COP) by using the two different formalisms are typically less than 10%. This gives rise to a useful and rapid design tool for the industry.
  • Keywords
    Modélisation , Performance , Modelling , Système à adsorption , Adsorption system , Silica gel , water , Performance , Gel de silice , EAU
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2007
  • Journal title
    International Journal of Refrigeration
  • Record number