Title of article
Two bed silica gel–water adsorption chillers: An effectual lumped parameter model
Author/Authors
Wang، نويسنده , , Xiaolin and Chua، نويسنده , , H.T.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
10
From page
1417
To page
1426
Abstract
This article develops an improved lump-parameter design model to investigate the water-circulation heat recovery scheme as applied to the two-bed silica gel–water adsorption chillers. We demonstrate that performance predictions stemming from this improved lump-parameter formalism compare favorably with experimental results at various conditions, particularly at the industrial rated conditions. We find that the present lump-parameter formalism adequately elucidates the water-circulation heat recovery scheme as does the distributed-parameter formalism. In the studied working condition of a two-bed silica gel–water adsorption chiller, the differences in cooling capacities and coefficients of performance (or COP) by using the two different formalisms are typically less than 10%. This gives rise to a useful and rapid design tool for the industry.
Keywords
Modélisation , Performance , Modelling , Système à adsorption , Adsorption system , Silica gel , water , Performance , Gel de silice , EAU
Journal title
International Journal of Refrigeration
Serial Year
2007
Journal title
International Journal of Refrigeration
Record number
1341681
Link To Document