• Title of article

    Frost retardation of an air-source heat pump by the hot gas bypass method

  • Author/Authors

    Byun، نويسنده , , Ju-Suk and Lee، نويسنده , , Jinho and Jeon، نويسنده , , Chang-Duk، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    7
  • From page
    328
  • To page
    334
  • Abstract
    This study is concerned with a hot gas (refrigerant) bypass method to retard the formation and propagation of frost in an air-source heat pump. The feasibility of the hot gas bypass method was investigated experimentally and the methodʹs performance is compared with that of a normal, 1.12 kW capacity air-source heat pump system with no defrost equipment such as an electric resistance heater. Results indicate that the hot gas bypass method is useful for retarding the formation and growth of frost at the outdoor coil. The best performance is shown under a bypass refrigerant flow rate of 0.2 kg/min (20% of the whole system refrigerant flow rate). During 210 min of heat pump operation, the hot gas bypass method improved COP and heating capacity at an average of 8.5% and 5.7%, respectively, relative to the normal system.
  • Keywords
    Experiment , Reduction , frost , Hot gas , Air-air , Pompe à chaleur , Expérimentation , Réduction , Givrage , Gaz chaud , Heat pump , Air-source
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2008
  • Journal title
    International Journal of Refrigeration
  • Record number

    1341727