Title of article
Frost retardation of an air-source heat pump by the hot gas bypass method
Author/Authors
Byun، نويسنده , , Ju-Suk and Lee، نويسنده , , Jinho and Jeon، نويسنده , , Chang-Duk، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
7
From page
328
To page
334
Abstract
This study is concerned with a hot gas (refrigerant) bypass method to retard the formation and propagation of frost in an air-source heat pump. The feasibility of the hot gas bypass method was investigated experimentally and the methodʹs performance is compared with that of a normal, 1.12 kW capacity air-source heat pump system with no defrost equipment such as an electric resistance heater. Results indicate that the hot gas bypass method is useful for retarding the formation and growth of frost at the outdoor coil. The best performance is shown under a bypass refrigerant flow rate of 0.2 kg/min (20% of the whole system refrigerant flow rate). During 210 min of heat pump operation, the hot gas bypass method improved COP and heating capacity at an average of 8.5% and 5.7%, respectively, relative to the normal system.
Keywords
Experiment , Reduction , frost , Hot gas , Air-air , Pompe à chaleur , Expérimentation , Réduction , Givrage , Gaz chaud , Heat pump , Air-source