Title of article
Experimental determination of the optimum performance of ejector refrigeration system depending on ejector area ratio
Author/Authors
Yap?c?، نويسنده , , R. and Ersoy، نويسنده , , H.K. and Aktoprako?lu، نويسنده , , A. and Halkac?، نويسنده , , H.S. and Yi?it، نويسنده , , O.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
7
From page
1183
To page
1189
Abstract
The performance of the ejector refrigeration system using ejectors with cylindrical mixing chamber is studied at operating conditions with choking in the mixing chamber. The condenser pressure is chosen so that the secondary flow choking can occur even in the ejector with the smallest area ratio. In the present study, the performance of the constructed system is determined by using six configurations of ejector and R-123 as working fluid in the system. The study is performed over a range of the ejector area ratio from 6.5 to 11.5 at the compression ratio 2.47. In the studied range, the experimental coefficient of performance of the system rises from 0.29 to 0.41, as the optimum generator temperature increases from 83 to 103 °C. Similar results were also found in the parametric study when the efficiencies of the nozzle and diffuser are taken as 0.90.
Keywords
Experiment , optimization , Performance , Parameter , Geometry , Expérimentation , Systéme frigorifique , Optimisation , Performance , Paramètre , Géométrie , système à éjecteur , Refrigeration system , Ejector system
Journal title
International Journal of Refrigeration
Serial Year
2008
Journal title
International Journal of Refrigeration
Record number
1341838
Link To Document