• Title of article

    Studies on the heating capacity control of a multi-type heat pump system applying a multi-input multi-output (MIMO) method

  • Author/Authors

    Lee، نويسنده , , Il Hwan and Choi، نويسنده , , Jong Won and Kim، نويسنده , , Min Soo، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2011
  • Pages
    13
  • From page
    416
  • To page
    428
  • Abstract
    This paper describes a method to control capacity of a multi-type heat pump system. Because indoor units are interconnected, alteration of the heating or cooling setting of one indoor unit can influence the performance of the other indoor units. Proportional-integral (PI) controllers were used to assess system performance, and the PI controllers’ gain values were optimized by using a genetic algorithm. A system model was established following a system identification optimization process, and a pseudo random binary sequence was selected as the system identification input signal. A multi-input multi-output (MIMO) controller was more effective in reducing such cross-coupling effects than a single-input single-output (SISO) controller. The temperature at the secondary fluid outlet in the condenser and the saturation pressure at the evaporator were selected as the control variables in the MIMO controller. The experimental results showed that an optimized MIMO controller could reduce overshoot by up to 40% compared with the results using a SISO controller.
  • Keywords
    Multi-output , System , Variable , INTEGRAL , Régulation de la puissance , Heat pump , Système , Variable , Pompe à chaleur , Multi-input , Régulation , Capacity control , Control , Grandeurs dיentrée , Intégral , Grandeurs de sortie
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2011
  • Journal title
    International Journal of Refrigeration
  • Record number