Title of article
First and second law investigation of waste heat based combined power and ejector-absorption refrigeration cycle
Author/Authors
Khaliq، نويسنده , , Abdul and Agrawal، نويسنده , , Basant K. and Kumar، نويسنده , , Rajesh، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2012
Pages
10
From page
88
To page
97
Abstract
In the proposed cogeneration cycle, a LiBr–H2O absorption refrigeration system is employed to the combined power and ejector refrigeration system which uses R141b as a working fluid. Estimates for irreversibilities of individual components of the cycle lead to possible measures for performance improvement. Results of exergy distribution of waste heat in the cycle show that around 53.6% of the total input exergy is destroyed due to irreversibilities in the components, 22.7% is available as a useful exergy output, and 23.7% is exhaust exergy lost to the environment, whereas energy distribution shows 44% is exhaust energy and 19.7% is useful energy output. Results also show that proposed cogeneration cycle yields much better thermal and exergy efficiencies than the previously investigated combined power and ejector cooling cycle. Current investigation clearly show that the second law analysis is quantitatively visualizes losses within a cycle and gives clear trends for optimization.
Keywords
ةjecteur , ABSORPTION , power , waste heat , Refrigeration system , ABSORPTION , Ejector , PRODUCTION , Système frigorifique , Récupération de chaleur