• Title of article

    Effect of inserting coiled wires on pressure drop of R-404A condensation

  • Author/Authors

    Salimpour، نويسنده , , Mohammad Reza and Gholami، نويسنده , , Hesam، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    7
  • From page
    24
  • To page
    30
  • Abstract
    In this study, an experimental investigation was carried out to determine the increase of pressure drop during convective condensation of R-404A vapor inside coiled wire inserted tubes. Experiments were performed for a plain tube and five coiled wire inserted tubes. Data were collected for four mass velocities. For each mass velocity, six different vapor qualities were considered. From the results, it is found that the coiled wire inserts increased the pressure drop up to 1200% compared to plain tube values. An empirical correlation is also developed to predict the pressure drop of coiled wire inserted tubes during R404-A condensation with accuracy of ±20%.
  • Keywords
    Pressure drop , R-404A , Chute de pression , Turbulator , Condensation , R404A , Turbulateur , Condensation
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2014
  • Journal title
    International Journal of Refrigeration
  • Record number

    1345939