• Title of article

    Design basis earthquakes for critical industrial facilities and their characteristics, and the Southern Hyogo prefecture earthquake, 17 January 1995

  • Author/Authors

    Shibata، نويسنده , , Heki، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1998
  • Pages
    13
  • From page
    157
  • To page
    169
  • Abstract
    This paper deals with how to establish the concept of the design basis earthquake (DBE) for critical industrial facilities such as nuclear power plants in consideration of disasters such as the Southern Hyogo prefecture earthquake, the so-called Kobe earthquake in 1995. The author once discussed various DBEs at the 7th World Conference on Earthquake Engineering. At that time, the author assumed that the strongest effective PGA would be 0.7 G, and compared the values of accelerations of a structure obtained by various codes in Japan and other countries. The maximum PGA observed by an instrument at the Southern Hyogo prefecture earthquake in 1995 exceeded the previous assumption of the author, even though the results of the previous paper had been pessimistic. According to the experience of the Kobe event, the author will point out the necessity of the third earthquake Ss adding to S1 and S2 of previous DBEs.
  • Journal title
    Reliability Engineering and System Safety
  • Serial Year
    1998
  • Journal title
    Reliability Engineering and System Safety
  • Record number

    1570680