Title of article
Influence of sand to coarse aggregate ratio on the interfacial bond strength of steel fibers in concrete for nuclear power plant
Author/Authors
Kim، نويسنده , , Jung Jin and Kim، نويسنده , , Dong Joo and Kang، نويسنده , , Su Tae and Lee، نويسنده , , Jang-Hwa Lee، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2012
Pages
10
From page
1
To page
10
Abstract
The interfacial bond strength of three high strength steel fibers (smooth, hooked, and twisted fiber) in concrete of nuclear power plants was investigated to develop fiber reinforced concrete for containment building. Sand to aggregate ratio (S/a) was adjusted to compensate reduction in the workability due to adding fibers; the influence of S/a ratio on the interfacial bond strength was investigated. As the S/a ratio increased from 0.444 to 0.615, the bond strength of twisted steel fiber was significantly improved while smooth and hooked steel fiber showed no clear difference. The different sensitivity according to the S/a ratio results from the different pullout mechanism: twisted steel fiber generates more mechanical interaction during fiber pullout at the interface between fiber and matrix than smooth and hooked fibers. The microscopic observation by scanning electron microscope back-scattered electrons images discovered lower porosity at the interfacial transition zone between fiber and concrete with higher S/a ratio.
Journal title
Nuclear Engineering and Design Eslah
Serial Year
2012
Journal title
Nuclear Engineering and Design Eslah
Record number
1592773
Link To Document