• Title of article

    A two-region simulation model of vertical U-tube ground heat exchanger and its experimental verification

  • Author/Authors

    Yang، نويسنده , , Weibo and Shi، نويسنده , , Mingheng and Liu، نويسنده , , Guangyuan and Chen، نويسنده , , Zhenqian، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    8
  • From page
    2005
  • To page
    2012
  • Abstract
    Heat transfer around vertical ground heat exchanger (GHE) is a common problem for the design and simulation of ground coupled heat pump (GCHP). In this paper, an updated two-region vertical U-tube GHE analytical model, which is fit for system dynamic simulation of GCHP, is proposed and developed. It divides the heat transfer region of GHE into two parts at the boundary of borehole wall, and the two regions are coupled by the temperature of borehole wall. Both steady and transient heat transfer method are used to analyze the heat transfer process inside and outside borehole, respectively. The transient borehole wall temperature is calculated for the soil region outside borehole by use of a variable heat flux cylindrical source model. As for the region inside borehole, considering the variation of fluid temperature along the borehole length and the heat interference between two adjacent legs of U-tube, a quasi-three dimensional steady-state heat transfer analytical model for the borehole is developed based on the element energy conservation. The implement process of the model used in the dynamic simulation of GCHPs is illuminated in detail and the application calculation example for it is also presented. The experimental validation on the model is performed in a solar-geothermal multifunctional heat pump experiment system with two vertical boreholes and each with a 30 m vertical 1 1/4 in nominal diameter HDPE single U-tube GHE, the results indicate that the calculated fluid outlet temperatures of GHE by the model are agreed well with the corresponding test data and the guess relative error is less than 6%.
  • Keywords
    Ground coupled heat pump , Two-region simulation model , experimental validation , Ground heat exchanger (GHE) , Vertical U-tube
  • Journal title
    Applied Energy
  • Serial Year
    2009
  • Journal title
    Applied Energy
  • Record number