Buckling length of a steel column for fire design
Author/Authors
Gomes، نويسنده , , Fernando C.T. and Providência e Costa، نويسنده , , Paulo M. M. Rodrigues، نويسنده , , Joمo Paulo C. and Neves، نويسنده , , Ildefonso C.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2007
Pages
6
From page
2497
To page
2502
Abstract
The Eurocode 3 part 1-2 gives some simple rules to determine the buckling length l f i of a steel column for fire design. In the case of a braced frame in which each storey comprises a separate fire compartment with sufficient fire resistance, Eurocode 3 suggests that the buckling length may be taken as l f i = 0.5 L in an intermediate storey and as l f i = 0.7 L in the top storey, where L is the system length in the relevant storey.
ity analyses for the evaluation of the buckling length and critical load of columns in braced frames show that the Eurocode 3 rule may be rather inaccurate in many practical situations. The authors propose alternative formulas to determine the buckling length at elevated temperatures, as an improvement of the actual rule of the Eurocode 3 part 1.2.
Keywords
Buckling , Column , Design , steel , fire