• Title of article

    Performance characteristics of a trickle fill in cross- and counter-flow configuration in a wet-cooling tower

  • Author/Authors

    Grobbelaar، نويسنده , , P.J. and Reuter، نويسنده , , H.C.R. and Bertrand، نويسنده , , T.P.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    10
  • From page
    475
  • To page
    484
  • Abstract
    In cooling towers packed with trickle or splash fills, which have almost isotropic or anisotropic flow resistance, the air flow through the fill is oblique or in cross-counterflow to the water flow, particularly at the cooling tower inlet when the fill loss coefficient is small or when the fill hangs down into the air inlet region. This results that the fill Merkel number or transfer characteristic for cross-counterflow is between that of purely counter- and cross-flow fills. sing CFD to model natural draught wet-cooling tower performance for isotropic or anisotropic fill resistance, two- or three-dimensional models and fill characteristics are therefore required to determine overall fill performance. s paper, the test facility, measurement techniques and methods of analysis used to determine fill performance characteristics in counter- and cross-flow configuration are presented and discussed. Results obtained for a specific fill are presented and discussed which can be used for the evaluation of cross-counterflow fill performance.
  • Keywords
    Wet-cooling , CrossFlow , Cooling Tower , Counterflow , Anisotropic , fill
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2013
  • Journal title
    Applied Thermal Engineering
  • Record number

    1904972