• Title of article

    Experimental analysis on frosting characteristic of SK-type finned refrigerating heat exchanger with large-diameter circular holes

  • Author/Authors

    Fang، نويسنده , , Zhao-song and Wang، نويسنده , , Hou-Hua and Zhang، نويسنده , , Jie and Wu، نويسنده , , Wei-wei، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    9
  • From page
    192
  • To page
    200
  • Abstract
    This paper presents the construction of both a plane fin-and-tube heat exchanger and a SK-type fin-and-tube heat exchanger. Based on plane fin-and-tube heat exchanger, comparative industrial prototype experiments of SK-type fin-and-tube heat exchanger energy efficiency performance were carried out in the artificial climate chamber. Test results confirmed several findings: when the amount of the refrigerant charged is the same and face velocity u = 3.75 m s−1, SK-type fin-and-tube heat exchanger refrigeration capacity increases by an average of 9.13%; energy consumption reduces by an average of 11.25%, coefficient of performance (COP) of heat exchanger increases by an average of 22.65% with continuous operation during the first 2 h. Also, when the operation time exceeds 2 h, the COP of both types of heat exchangers are both less than 0.6, illustrating that under frost conditions, the defrost interval should not be too long, otherwise energy consumption may sharply spike.
  • Keywords
    SK-type fin , Heat transfer enhancement , Energy efficiency performance , Prototype frost test
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2014
  • Journal title
    Applied Thermal Engineering
  • Record number

    1906768