Title of article
Diagnosis of Heat Exchanger Scales in Cooling Water Systems
Author/Authors
-، - نويسنده Chemical and Petrochemical Division, Research Institute of Petroleum Industry, P.O. Box: 18745-4163 Tehran, I.R. IRAN Kameli, Mohammad , -، - نويسنده Chemical and Petrochemical Division, Research Institute of Petroleum Industry, P.O. Box: 18745-4163 Tehran, I.R. IRAN Esmaeili, Naser , -، - نويسنده Chemical and Petrochemical Division, Research Institute of Petroleum Industry, P.O. Box: 18745-4163 Tehran, I.R. IRAN Rahimi Mofrad, Hossein
Issue Information
فصلنامه با شماره پیاپی 45 سال 2008
Pages
8
From page
65
To page
72
Abstract
-
Abstract
An experimental database is compiled in order to fingerprint the scales formed over the hot surfaces of heat exchangers, in cooling water systems or other systems with similar chemistry. To collect these data, a dynamic simulating pilot plant was designed with considerable application flexibility among which simultaneous flow of water with different velocity and heat fluxes to three simulating heat exchangers can be mentioned. Changing the water chemistry and using various inhibitors composition known in the art, the nature of scale deposits formed on the heating elements was studied by scanning electron microscopy (SEM) coupled with Energy Dispersive X-ray instrument. The heat flux of the elements ranges from 9.46 × 104 to 1.45 × 105 J/m2.sec, which depending on the velocity of fluid passing through the orifice of pipe, give rise to skin temperatures of 80 °C to 230 °C. The flow velocities used in this study were 0.21 and 0.46 m/sec. Phosphonates and most popular polymers were studied as scale inhibitors.
Journal title
Iranian Journal of Chemistry and Chemical Engineering (IJCCE)
Serial Year
2008
Journal title
Iranian Journal of Chemistry and Chemical Engineering (IJCCE)
Record number
2151877
Link To Document