• Title of article

    Second law analysis of double effect vapour absorption cooler system

  • Author/Authors

    Gomri، نويسنده , , Rabah and Hakimi، نويسنده , , Riad، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    6
  • From page
    3343
  • To page
    3348
  • Abstract
    In this paper, exergy analysis of double effect lithium bromide/water absorption refrigeration system is presented. The system consists of a second effect generator between the generator and condenser of the single effect absorption refrigeration system, including two solution heat exchangers between the absorber and the two generators. er to simulate the refrigeration system by using a computer, a new set of computationally efficient formulations of thermodynamic properties of lithium bromide/water solution developed is used. The exergy analysis is carried out for each component of the system. All exergy losses that exist in double effect lithium bromide/water absorption system are calculated. In addition to the coefficient of performance and the exergetic efficiency of the system, the number of exergy of each component of the system is also estimated. tudy suggests the component of the absorption refrigeration system that should be developed. The results show that the performance of the system increases with increasing low pressure generator (LPG) temperature, but decreases with increasing high pressure generator (HPG) temperature. The highest exergy loss occurs in the absorber and in the HPG, which therefore makes the absorber and HPG the most important components of the double effect refrigeration system.
  • Keywords
    Energy , Exergy , Double effect , Modelling , Absorption cooler , H2O–LiBr
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2008
  • Journal title
    Energy Conversion and Management
  • Record number

    2334314