• Title of article

    Experimental study on the thermal performance of a mechanical cooling tower with different drift eliminators

  • Author/Authors

    Lucas، نويسنده , , M. and Martيnez، نويسنده , , P.J. and Viedma، نويسنده , , A.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    8
  • From page
    490
  • To page
    497
  • Abstract
    Cooling towers are equipment devices commonly used to dissipate heat from power generation units, water-cooled refrigeration, air conditioning and industrial processes. Water drift emitted from cooling towers is objectionable for several reasons, mainly due to human health hazards. It is common practice to fit drift eliminators to cooling towers in order to minimize water loss from the system. It is foreseeable that the characteristics of the installed drift eliminators, like their pressure drop, affect the thermal performance of the cooling tower. However, no references regarding this fact have been found in the reviewed bibliography. This paper studies the thermal performance of a forced draft counter-flow wet cooling tower fitted with different drift eliminators for a wide range of air and water mass flow rates. The data registered in the experimental set-up were employed to obtain correlations of the tower characteristic, which defines the cooling tower’s thermal performance. The outlet water temperature predicted by these correlations was compared with the experimentally registered values obtaining a maximum difference of ±3%.
  • Keywords
    Cooling Tower , Drift eliminator , Thermal Performance
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2009
  • Journal title
    Energy Conversion and Management
  • Record number

    2334503