• Title of article

    An improved model and the thermodynamic calculation method for tailrace tunnel ventilating system in hydropower station

  • Author/Authors

    Yu، نويسنده , , Yanshun and Zhang، نويسنده , , Shaofan and Li، نويسنده , , Xianting، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    7
  • From page
    2060
  • To page
    2066
  • Abstract
    Tailrace tunnel ventilating can be used as a highly efficient and energy saving air conditioning for factory buildings in hydropower station. This paper describes an improved model of heat and moisture transfer for tailrace tunnel ventilating system with the assumption of thermal insulated for the tunnel wall and with the same temperature at any cross section as the wet bulb temperature of that air, and the improved model has been validated against the field test from Yingxiuwan hydropower station and compared with the reference simplified model, the results show that the improved model has a good agreement with the field test data and a better precision than the reference simplified model for the performance prediction of heat and moisture transfer of tailrace tunnel ventilating, especially for the short tunnel system. Moreover, the thermodynamic calculation method of heat and moisture transfer is presented, and the method is intended for use in annual performances prediction or design tools for tailrace tunnel ventilating system in hydropower station.
  • Keywords
    improved model , Heat and moisture transfer , Thermodynamic calculation method , Tailrace tunnel ventilating system
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2009
  • Journal title
    Energy Conversion and Management
  • Record number