• Title of article

    A systemic approach for optimal cooling tower operation

  • Author/Authors

    Cortinovis، نويسنده , , Giorgia F. and Paiva، نويسنده , , José L. and Song، نويسنده , , Tah W. and Pinto، نويسنده , , José M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    10
  • From page
    2200
  • To page
    2209
  • Abstract
    The thermal performance of a cooling tower and its cooling water system is critical for industrial plants, and small deviations from the design conditions may cause severe instability in the operation and economics of the process. External disturbances such as variation in the thermal demand of the process or oscillations in atmospheric conditions may be suppressed in multiple ways. Nevertheless, such alternatives are hardly ever implemented in the industrial operation due to the poor coordination between the utility and process sectors. The complexity of the operation increases because of the strong interaction among the process variables. In the present work, an integrated model for the minimization of the operating costs of a cooling water system is developed. The system is composed of a cooling tower as well as a network of heat exchangers. After the model is verified, several cases are studied with the objective of determining the optimal operation. It is observed that the most important operational resources to mitigate disturbances in the thermal demand of the process are, in this order: the increase in recycle water flow rate, the increase in air flow rate and finally the forced removal of a portion of the water flow rate that enters the cooling tower with the corresponding make-up flow rate.
  • Keywords
    Cooling Tower , Nonlinear programming , Process Analysis , optimization , Cooling water system
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2009
  • Journal title
    Energy Conversion and Management
  • Record number

    2334842