• Title of article

    Part load efficiency of packaged air-cooled water chillers with inverter driven scroll compressors

  • Author/Authors

    Cecchinato، نويسنده , , Luca، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2010
  • Pages
    10
  • From page
    1500
  • To page
    1509
  • Abstract
    In this paper different packaged air-cooled systems, operating on scroll compressors, are experimentally analysed from the point of view of the relation between energy efficiency and actual capacity. Single compressor, double compressors and double compressors with uneven volumetric capacity units are tested. Experimental tests demonstrated that cooling capacity control by means of variation of rotational speed is an suitable solution for improving the part load efficiency of these systems. Step capacity units obtained by splitting the system volumetric capacity between two compressors are also effective solutions. Nevertheless they appear to be more efficient than single inverter driven chillers only for part load conditions lower than 60%. In the analysed cooling capacity range (25–50 kW), tandem compressors chillers with one inverter driven compressor appear the most efficient solution combining rotational speed with step capacity control. Seasonal energy efficiency ratios were obtained with prEN 14825 calculation method confirming reduced energy consumption associated to continuous and step cooling capacity control.
  • Keywords
    Capacity reduction , efficiency , Energy consumption , Inverter , Water chiller , Scroll compressor
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2010
  • Journal title
    Energy Conversion and Management
  • Record number