• Title of article

    Analytical solutions for evaluating the thermal performances of wet air cooling coils under both unit and non-unit Lewis Factors

  • Author/Authors

    Xia، نويسنده , , Liang and Chan، نويسنده , , M.Y. and Deng، نويسنده , , S.M. and Xu، نويسنده , , X.G.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2010
  • Pages
    8
  • From page
    2079
  • To page
    2086
  • Abstract
    Analytical solutions for evaluating the thermal performances of both chilled water wet cooling coils and direct expansion (DX) wet cooling coils, respectively, under both unit and non-unit Lewis Factors are developed and reported in this paper. The analytical solution was validated by comparing its predictions with those from numerically solving the fundamental governing equations of heat and mass transfer taking place in a wet cooling coil. With the analytical solutions, the distributions of air temperature and humidity ratio along air flow direction in a wet cooling coil can be predicted, and the differences in the thermal performances of the cooling coils under both unit and non-unit Lewis Factors can be identified. The analytical solutions, on one hand, can be a low-cost replacement to numerically solving the fundamental heat and mass transfer governing equations, and on the other hand, is able to deal with evaluating thermal performance for wet air cooling coils operated under both unit and non-unit Lewis Factors.
  • Keywords
    Lewis Factor , Heat and mass transfer , analytical solutions , Wet cooling coils
  • Journal title
    Energy Conversion and Management
  • Serial Year
    2010
  • Journal title
    Energy Conversion and Management
  • Record number