Title of article
Experimental study of hydronic panels system and its environment
Author/Authors
Dيaz، نويسنده , , Néstor Fonseca، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
11
From page
770
To page
780
Abstract
An experimental analysis of hydronic cooling or heating ceiling panels coupled to the building is present in this investigation as a part of the commissioning study of this system. Two test chambers are adapted in a way to reproduce the interaction of the system to the building (windows, internal thermal loads distribution, building structure and ventilation). A series of experimental tests were performed in which the main objective is to observe the influence of parameters such as the water mass flow rate, supply water temperature, thermal load distribution, window and ventilation system effects on the hydronic ceiling capacity and comfort conditions. Test results show that the influence of asymmetric surfaces temperatures inside the room, especially the window effect is not negligible. Then, it is clear that the cooling hydronic ceiling must be evaluated coupled to the building systems and structure.
Keywords
radiation , Experimental , Building , Hydronic panels
Journal title
Energy Conversion and Management
Serial Year
2011
Journal title
Energy Conversion and Management
Record number
2335435
Link To Document