Title of article
Analytical calculation of detailed model parameters of cast resin dry-type transformers
Author/Authors
Eslamian، نويسنده , , M. and Vahidi، نويسنده , , B. and Hosseinian، نويسنده , , S.H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
10
From page
2565
To page
2574
Abstract
Non-flammable characteristic of cast resin dry-type transformers make them suitable for different kind of usages. This paper presents an analytical method of how to obtain parameters of detailed model of these transformers. The calculated parameters are compared and verified with the corresponding FEM results and if it was necessary, correction factors are introduced for modification of the analytical solutions. Transient voltages under full and chopped test impulses are calculated using the obtained detailed model. In order to validate the model, a setup was constructed for testing on high-voltage winding of cast resin dry-type transformer. The simulation results were compared with the experimental data measured from FRA and impulse tests.
Keywords
Cast resin dry-type transformer , Parameter calculation , Detailed model , Impulse test , FEM , FRA
Journal title
Energy Conversion and Management
Serial Year
2011
Journal title
Energy Conversion and Management
Record number
2335681
Link To Document