Title of article
Modeling and calculation of open carbon dioxide refrigeration system
Author/Authors
Cai، نويسنده , , Yufei and Zhu، نويسنده , , Chunling and Jiang، نويسنده , , Yanlong and Shi، نويسنده , , Hong، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2015
Pages
7
From page
92
To page
98
Abstract
Based on the analysis of the properties of carbon dioxide, an open carbon dioxide refrigeration system is proposed, which is responsible for the situation without external electricity unit. A model of open refrigeration system is developed, and the relationship between the storage environment of carbon dioxide and refrigeration capacity is conducted. Meanwhile, a test platform is developed to simulation the performance of the open carbon dioxide refrigeration system. By comparing the theoretical calculations and the experimental results, several conclusions are obtained as follows: refrigeration capacity loss by heat transfer in supercritical state is much more than that in two-phase region and the refrigeration capacity loss by remaining carbon dioxide has little relation to the state of carbon dioxide. The results will be helpful to the use of open carbon dioxide refrigeration.
Keywords
Supercritical state , Carbon dioxide , Two-phase region , Open refrigeration system , Refrigeration capacity loss
Journal title
Energy Conversion and Management
Serial Year
2015
Journal title
Energy Conversion and Management
Record number
2338752