Title of article
Fast identification of O2 corrosion in economiser tubes
Author/Authors
Qua، نويسنده , , HockChye and Khaw، نويسنده , , ChwinChieh and Tan، نويسنده , , ChingSeong and Wang، نويسنده , , Xin and Ooi، نويسنده , , JongBoon، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
10
From page
2201
To page
2210
Abstract
Failure investigation was conducted on three tube samples via visual/metallographic examination and analysis of operational history. The investigation employed a fast-identification approach, which allowed a shorter down time and faster production recovery after tube failure. Visual and metallographic evidence showed that the tube samples had suffered from abnormally high wastage at the external and internal surfaces; the latter surface, in addition had suffered from deep pitting. Analysis of operational history confirmed the presence of dissolved O2 in the feedwater. It was concluded that leakage was primarily caused by tube thinning from internal wastage/pitting, aggravated by external wastage.
Keywords
Economiser tube , Pitting corrosion , Metallography , Boiler Failure
Journal title
Engineering Failure Analysis
Serial Year
2011
Journal title
Engineering Failure Analysis
Record number
2339441
Link To Document