• Title of article

    Fire safety distances for open pool fires

  • Author/Authors

    Sudheer، نويسنده , , S. and Kumar، نويسنده , , Lokendra and Manjunath، نويسنده , , B.S. and Pasi، نويسنده , , Amit and Meenakshi، نويسنده , , G. and Prabhu، نويسنده , , S.V.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    9
  • From page
    265
  • To page
    273
  • Abstract
    Fire accidents that carry huge loss with them have increased in the previous two decades than at any time in the history. Hence, there is a need for understanding the safety distances from different fires with different fuels. Fire safety distances are computed for different open pool fires. Diesel, gasoline and hexane are used as fuels for circular pool diameters of 0.5 m, 0.7 m and 1.0 m. A large square pool fire of 4 m × 4 m is also conducted with diesel as a fuel. All the prescribed distances in this study are purely based on the thermal analysis. IR camera is used to get the thermal images of pool fires and there by the irradiance at different locations is computed. The computed irradiance is presented with the threshold heat flux limits for human beings.
  • Keywords
    Irradiance , IR camera , Open pool fires , Fire safe distances , heat flux
  • Journal title
    Infrared Physics & Technology
  • Serial Year
    2013
  • Journal title
    Infrared Physics & Technology
  • Record number

    2376422