Title of article
Study on detection for the defects of XLPE cable lines
Author/Authors
Uchida، نويسنده , , K.، نويسنده , , Kobayashi، نويسنده , , S.، نويسنده , , Kawashima، نويسنده , , T.، نويسنده , , Tanaka، نويسنده , , H.، نويسنده , , Sakuma، نويسنده , , S.، نويسنده , , Hirotsu، نويسنده , , K.، نويسنده , , Inoue، نويسنده , , H.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
6
From page
663
To page
668
Abstract
This paper is a report on the results of a basic study of testing
methods to replace the dc after laying test that is presently most frequently used
as an after laying test for XLPE cable lines. Chosen as the alternative
waveforms for dc voltage were damped oscillating wave (OSW) and very-lowfrequency
wave (VLF) voltage. Experiments were conducted on the ability to
detect various types of lme defects under these voltages. It was found that
these alternative waveforms are promising as after laying teʹst voltage
waveforms to replace dc and that greater defect detection ability can be
achieved by combining them when conducting tests.
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1996
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399112
Link To Document