Title of article
Analysis of internal winding stresses in EHV generator step-up transformer failures
Author/Authors
Morched، نويسنده , , A.S.، نويسنده , , Marti، نويسنده , , L.، نويسنده , , Brierley، نويسنده , , R.H.، نويسنده , , Lackey، نويسنده , , J.G.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
7
From page
888
To page
894
Abstract
This paper descrjbes studies carried out to investigate the
failure of one phase of a 990 MVA generator step-up
transformer bank at one of Ontario Hydroʹs major generating
stations. A high accuracy frequency dependent transformer
model was used to determine the behaviour of the transformer
at the terminals under transient conditions. With this
information, and with measured transfer functions between the
terminals and various points inside the windings, it was
possible to create internal voltage distribution maps. This
information was then used to evaluate the insulation stresses
within the winding, and to ascertain that the use of additional
capacitance at the HV terminals to reduce the magnitude and
frequency of incoming transients would be adequate to reduce
the disk-to-disk stresses near the line end of the HV winding.
The values of the HV terminal capacitances were chosen so
that no undue stresses in other portions of the winding would
take place.
Keywords
Transformer Internal Resonances , Winding Transfer Functions , EMTP. , Transformer Failure