• Title of article

    Analysis of internal winding stresses in EHV generator step-up transformer failures

  • Author/Authors

    Morched، نويسنده , , A.S.، نويسنده , , Marti، نويسنده , , L.، نويسنده , , Brierley، نويسنده , , R.H.، نويسنده , , Lackey، نويسنده , , J.G.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 1996
  • Pages
    7
  • From page
    888
  • To page
    894
  • Abstract
    This paper descrjbes studies carried out to investigate the failure of one phase of a 990 MVA generator step-up transformer bank at one of Ontario Hydroʹs major generating stations. A high accuracy frequency dependent transformer model was used to determine the behaviour of the transformer at the terminals under transient conditions. With this information, and with measured transfer functions between the terminals and various points inside the windings, it was possible to create internal voltage distribution maps. This information was then used to evaluate the insulation stresses within the winding, and to ascertain that the use of additional capacitance at the HV terminals to reduce the magnitude and frequency of incoming transients would be adequate to reduce the disk-to-disk stresses near the line end of the HV winding. The values of the HV terminal capacitances were chosen so that no undue stresses in other portions of the winding would take place.
  • Keywords
    Transformer Internal Resonances , Winding Transfer Functions , EMTP. , Transformer Failure
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    1996
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number