Title of article
Fault component reactance relay
Author/Authors
Shengshi Zhu، نويسنده , , Yibao Xing، نويسنده , , Fenghai Sui، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
9
From page
1292
To page
1300
Abstract
A new distance relay is developed in this paper.The relay is based on two operation criteria - - - - acurrent criterion and a voltage criterion. Eachuses the fault component as operating quantity, andthe relay reacts only on the reactance of the trans-mission line. So, it is a fault component reactancerelay. During external fault, two criteria arecomplementary each other, i. e. at least one of themrill not be satisfied. So no maloperation will
happen. During internal fault both criteria will be
satisfied even if the fault resistance is high.
Keywords
Distance relay , fault component , reactance relay