Title of article
Radio and audible noise performance of T2 conductors
Author/Authors
Chartier، نويسنده , , V.L.، نويسنده , , Lowder، نويسنده , , S.M.، نويسنده , , Rodick، نويسنده , , S.، نويسنده , , Vogt، نويسنده , , M.W.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 1996
Pages
11
From page
1464
To page
1474
Abstract
Central Iowa Power Cooperative (CIPCO) plans to
build a 345-kV line using a bundle of four Partridge T2 conductors.
T2 conductor is two normal cylindrical conductors
twisted together to prevent galloping during freezing rain and
wind. Since it was not known whether any of the analytical
expressions for calculating the radio and audible noise performance
of conductors would work for T2 conductors, measurements
were performed in the Bonneville Power Administration’s
(BPA) high voltage laboratory to compare the radio
influence voltage (RIV) and audible noise (AN) performance
of the Partridge T2, Partridge and Dove conductors. The Dove
conductor has about the same cross section and current carrying
capacity as the Partridge T2 conductor. The tests showed
that no consistent, measurable difference could be found in
the RIV and AN levels between the Partridge T2 and Dove
conductors under dry or artificial rain conditions and whether
the conductors were arranged in bundles of 4, 3, or 2 subconductors
or as single conductors.
Keywords
corona , audible noise , radio noise , transmissionlines , T2 conductor
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
1996
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
399211